Confirmed website product scope
The following figures come from the latest supplied SecuriSmoke ASD product brochure V2.0. Alarm sensitivity and pre-signal sensitivity are stated separately, and EN 54-20 tube-network limits are not mixed with other configuration limits.
- ASD 535-3: one channel with smoke-level indicator; 2,880 m²; 300 m EN 54-20 tube network; class A / B / C holes 18 / 56 / 120; alarm 0.02%–10%/m; pre-signal from 0.002%/m; IP54; −30 to +60°C
- ASD 535-4: two independent channels with smoke-level indicators; 5,760 m²; 2 × 300 m EN 54-20 tube network; class A / B / C holes 35 / 112 / 240; alarm 0.02%–10%/m; pre-signal from 0.002%/m; IP54; −30 to +60°C
- ASD 532: one channel with smoke-level indicator; 1,280 m²; 120 m EN 54-20 tube network; class A / B / C holes 8 / 12 / 16; alarm 0.02%–10%/m; pre-signal from 0.002%/m; IP54; −20 to +60°C
- ASD 531: one channel; 720 m²; 75 m EN 54-20 tube network; class A / B / C holes 6 / 8 / 12; alarm 0.02%–10%/m; pre-signal from 0.006%/m; IP54; −10 to +55°C